Globe - 3 Way Mixing, 3 Way Diverting Control Valves | Series 3500

globe valves, 3 way mixing, 3 way diverting control valves

1" to 10" body size, ANSI Class 150-600 with flanged, butt-weld, or socket-weld ends. Available in Carbon Steel or Alloy Steel or Stainless Steel body materials. Automated with Diaphragm and Cylinder Actuators with/without Handwheels. Positioners, Instrument Valves, Limit Swithces and Solenoid Valves are available.

  • Flow Direction: Mixing, Diverting
  • Max. Fluid Temperature: 1049°F
  • Minimum Fluid Temperature: -320°F
  • Seat Leakages: ANSI B16.104 Class IV
    • Option 1: ANSI B16.104 Class V for Metal Seat Tight Shutoff
    • Option 2: ANSI B16.104 Class VI for Teflon Soft Seat & Seal (-22°F ~ 446°F)
  • Body: Globe Single Seated Top Guide
  • Bonnet Type: Stud Bolted
    • Standard Type: -0.4°F ~ 536°F
    • Extension Type: 538 °F ~ 1049°F & under -0.4°F
  • Flow Characteristics: Linear, Equal Percentage, Modified %
  • Cv Ration: 50:1
  • Diaphragm actuators enclosed, heavy duty cylinders (spring-cylinder and double cylinder) available
  • Applicable for various instruments (positioner, SOV, Limit switch)

A Wide Range of Control Valves

JFlow Controls offers a wide range of control valves, from the most simple “V-notch” ball control valves to segmented V-ball and engineered globe control valves. JFlow’s broad product offering and use of our own control valve sizing program, allow us to analyze customer’s requirement and apply the best valve for the application. J-Flow has an excellent track record of saving customer’s money by providing the least expensive type of valve without compromising performance.

All modulating control valve quotes are provided with a Control Valve Sizing Data Sheet to ISA standards. Noise and cavitation prediction data is also included. J-Flow globe control valves utilize a variety of special trims to reduce noise or reduce and/or eliminate potential cavitation. Latest technology accessories include positioners and other communication devices that incorporate pneumatic, analog (I/P), and digital technologies (HART, Profibus, Foundation Fieldbus, AS-I, wireless).